The use of ducts to improve the control of supply air temperature rise in UFAD systems: CFD and lab study
Introduction
Underfloor air distribution (UFAD) systems use open spaces, called plenums, between the structural slab and raised floor panels to supply conditioned air into the occupied zone [1]. During the past two decades these systems have offered an alternative to traditional overhead (OH) systems, and are now commonly used all over the world. There are several potential advantages of using UFAD systems compared to OH systems:
- •
improved thermal comfort [1], [2], [3];
- •
improved indoor air quality [1], [3];
- •
reduced life cycle costs [1];
- •
reduce floor-to-floor height in new construction.
Among all features that characterize UFAD technology, room air stratification and temperature rise in the underfloor plenum play key roles in determining the operational success of these systems.
Under cooling operation, a properly controlled UFAD system produces air stratification in the conditioned space [4], resulting in higher temperatures at the ceiling level compared to the floor. Room air stratification has been widely investigated during the years with case studies, laboratory tests, and energy models [4], [5], [6], [7].
Temperature rise in the underfloor plenum is due to convective heat gain to the conditioned supply air as it travels through the underfloor supply plenum [8]. Bauman et al. [9] demonstrated using a steady-state model that the magnitude of heat transfer into the underfloor plenum through the raised floor and the floor slab is 35–45% of the total zone cooling load. Schiavon et al. [10], using whole-building energy simulations, found that the total heat transfer into the plenum is of similar magnitude, 22–37% of the total zone peak UFAD cooling load, depending on interior or perimeter zone location. The work done by Woods and Novosel [11] also provides clear evidence of the temperature rise in the underfloor plenum and its magnitude. In their study the researchers performed a comparative analysis of conventional overhead (OH) and UFAD system performance. They found that the room heat extraction rate for the UFAD system is 35–64% of the instantaneous heat gain to the room, compared to the OH system, where it is 66–93%. The authors found the cause of this difference to be the heat entering the supply plenum. The magnitude of the plenum heat gain can be quite high, and the warmer supply air temperature can make it difficult to maintain comfort in the occupied space (without increasing airflow rates), particularly in perimeter zones where cooling loads reach their highest levels [1]. How to predict and account for plenum thermal performance is one of the key design issues facing practicing engineers.
In a building conditioned with a UFAD system a desirable scenario would be to deliver the coolest supply air into perimeter plenum zones, allowing warmer plenum temperatures in interior zones. However, due to the common building HVAC configuration with primary supply air ducts in the building core, conditioned air is typically supplied into interior portions of the underfloor plenum and flows out to perimeter zone locations. As a results of the temperature rise in the plenum, buildings equipped with an open underfloor plenum system will tend to have warmer supply air entering the perimeter zone, and colder air into the interior zone. Three recommended approaches to improve the control of supply air temperature rise in UFAD systems are as follows [1]:
- •
Use ductwork to deliver cool air to/towards the perimeter. This is the subject of this research work.
- •
Direct plenum inlets with higher inlet velocities toward critical perimeter locations.
- •
Instead of the typical interior plenum inlet locations, consider designing the plenum with perimeter inlets (shafts), if possible.
In terms of the first recommended strategy above, the advantage of using ductwork is that it eliminates direct contact along the length of the duct with the slab and underside of the raised floor panels, thereby reducing temperature gain to the supply air. One disadvantage is the added flow resistance caused by the duct in comparison to airflow through an open plenum, which tends to increase the pressure drop through the system and required fan energy. In addition, once the supply air exits the duct and enters the plenum, it is still exposed to the same heat transfer from the top and bottom surfaces. The challenge and goal of this research is to develop a validated CFD model of underfloor air supply plenums equipped with flexible (or rigid) ducts.
Several experiments were carried out in a full-scale underfloor plenum test facility, in order to characterize all the phenomena that take place in an underfloor plenum equipped with a fabric duct. Fabric ducts were chosen due to their ease of installation and flexibility once installed. Experimental data were collected for validation of a computational fluid dynamics (CFD) model of the plenum. This paper describes the first part of a more comprehensive work, whose aim is to use the validated CFD plenum model to conduct simulations of a broader range of plenum design and operational parameters. In particular the validated model will be used to compare the use of ductwork, to deliver cool air to/towards the perimeter vs. the use of plenum inlets with higher inlet velocities (the CFD model for this previous open plenum configuration was developed by Jin et al. [12] using the same plenum test facility), in order to highlight the limits and the capabilities of these two technical solutions to reduce the temperature rise in the underfloor plenum.
Section snippets
Methods
The technical approach includes the following tasks:
- (1)
Full-scale experiments in underfloor plenum test facility.
- (2)
Development of computational fluid dynamics (CFD) model of underfloor plenum.
- (3)
Validation of CFD plenum model by comparison with full-scale experimental database.
Test measurement results and discussion
The most important information is related to the diffusers, because they can be considered as the interface between the supply plenum and the room. The airflow through each diffuser was measured with the airflow-meter. As shown in Fig. 4, the airflows through the four perimeter diffusers are on average higher than for the interior diffusers. This is due to the VAV diffuser’s damper setting.
It is also interesting to see that in configuration #2, even if the four perimeter VAV diffusers are all
Conclusions
The tests conducted using the underfloor plenum facility have demonstrated the rise in air temperature as it flows through the underfloor plenum. The tests proved also that using fabric ducts (as well as rigid ducts) to deliver cool air directly into the plenum perimeter “reverses” the typical temperature distribution, with colder air in the perimeter and warmer air in the interior zone.
Using the test results it was possible to make two detailed CFD models of the underfloor plenum equipped with
References (19)
- et al.
Impact of plenum thermal decay on underfloor air distribution (UFAD) system performance
Appl Energy
(2012) - et al.
Simplified calculation method for design cooling loads in underfloor air distribution (UFAD) systems
Energy Build
(2011) - et al.
The numerical computation of turbulent flows
Comput Meth Appl Mech Energy
(1974) Underfloor air distribution (UFAD) design guide
ASHRAE
(2013)- et al.
Integrated design and UFAD
ASHRAE J
(2009) - et al.
Performance of underfloor air distribution in a field setting
Int J Vent
(2005) - Bauman F, Webster T, Linden P, Buhl F. Energy performance of underfloor air distribution systems. In: PIER final...
- et al.
Underfloor air distribution: thermal stratification
ASHRAE J
(2002) - Webster T, Bauman F, Reese J, Shi M. Thermal stratification performance of underfloor air distribution (UFAD) systems....
Cited by (18)
Hydro-thermal performance of fabric air duct (FAD): Experimental and CFD simulation assessments
2023, Case Studies in Thermal EngineeringPredicting the thermal comfort of occupants in an indoor auditorium space with different UFAD ventilation arrangements
2023, Materials Today: ProceedingsResearch on a new optimization method for airflow organization in breeding air conditioning with perforated ceiling ventilation
2022, EnergyCitation Excerpt :Ignore the influence of lines, pipes and supports in the plenum, as well as the influence of some facilities such as corridors, pillars and pig troughs. In view of the constrains and assumptions in the simulation, the airflow environment is in a continuous and stable state, and the steady-state simulation is selected as the model of the fluid flow state [35,36]. The direction of gravitational acceleration is vertically downward, and the magnitude is 9.8 m/s2.
Investigation on pre-cooling potential of UFAD via model-based predictive control
2022, Energy and BuildingsCitation Excerpt :The increased energy consumption of the UFAD could be avoided by increasing the insulation between the room and the plenum. On the other hand, ductwork added under the plenum could resolve the supply air temperature increase, which was investigated using a CFD simulation [19]. The higher energy consumption of the UFAD reported by Yu et al. [24] is somewhat controversial compared to Xue and Chen [21].
Influences of different operational configurations on combined effects of room air stratification and thermal decay in UFAD system
2018, Energy and BuildingsCitation Excerpt :In addition, the EnergyPlus can reflect the room air stratification in simulation environment through the Gamma-Phi Correlation of the room air model object. These capacity of EnergyPlus for UFAD system were validated and continuously improved through many researches and tests under various conditions [1,2,9–11,19,20,24–33]. For more information about validation of the EnergyPlus program, see [34].
Investigation into air distribution systems and thermal environment control in chilled food processing facilities
2018, International Journal of RefrigerationCitation Excerpt :In general, CFD numerical studies applied to different refrigerated spaces for food conservation show that prediction of air velocity, temperature distribution and mean age of the air in these spaces can be obtained in good agreement with experimental data (Chanteloup and Mirade, 2009; Chourasia and Goswami, 2007a, 2007b, 2007c; Ho et al., 2010). Also, numerical studies involving stratified air temperature are also available for the performance analysis of underfloor air distribution systems (Fathollahzadeh et al., 2015; Pasut et al., 2014; Zhang et al., 2016), or for the optimization of thermal comfort and energy savings (Cheng et al., 2012, 2013; Ning et al., 2016). Lastly, Tassou et al. (2015) provided a review of modelling approaches of chilled spaces in the cold food chain.